Item number: GTZ4121000R0002

Current Transformers for monitoring heat current

  • Current Transformers for monitoring heat current

The GTZ4121 current transformer acquires heating current and is used in combination with a controller for heat current monitoring. It is capable of transforming up to 4 alternating currents into 4 different direct voltages. The three line currents in 3-phase systems are transformed into a summated voltage when appropriately wired.

  • Technical characteristics

    Input

    • 3 or 4 straight-through current transformers, 8.8 mm hole diameter
    • 0...40 AAC, 0...20 AAC, 0...10 AAC, 0...5 AAC
    • Power consumption: 0.25 W per transformer

    Output

    • 0...10 VDC, short-circuit proof

    Response Characteristics

    • Accuracy: 5% of reading
    • Output voltage: U=0.2345*I -0.015 (U in V, I in A)

    • For mounting to top-hat rail
    • Dimensions (LxWxD) 93 x 82.5 x 63 mm