Item number: 535-

Measuring transducer for frequency difference

  • Measuring transducer for frequency difference

Applications

Transducer for the conversion of the difference in frequency from two electrical systems requiring synchronization into a direct current or voltage signal which is proportional to the measured value.

  • Technical characteristics
    • Measurement inputs for sinusoidal, square-wave or distorted nominal input voltages with dominant fundamental wave
    • Input voltage: 10 to 690 V
    • Auxiliary power: 85 to 230 V AC/DC
    • Input frequency response time periods: 4
    • Measuring range limits:
    • df ± 1% fS to ± 80% fS, fS and fG= 10 Hz to 1.5 kHz
    • fS = bus bar frequency, fG = generator frequency
    • Measurement output available with unipolar, bipolar or live-zero output quantities
    • Measuring method: digital period of oscillation measurement
    • Power supply: integrated AC-DC power pack with large tolerance range for universal use
    • Maritime product features (formerly GL, Germanischer Lloyd) / suitable for use on ocean-going vessels
    • Housing:
    • SINEAX: P13/70 housing for top-hat rail mounting
    • EURAX: plug-in module (7 standard width units) for 19" rack
    • CSA certificate , German Lloyd approval