Portfolio of Universal Measurement Devices |
|||||||||
Measurement System | AM2000 | AM3000 | APLUS | A2000 | CAM | A210 / A220 | A230s / A230 | M56x Series | DME 4xx Series |
---|---|---|---|---|---|---|---|---|---|
Measurement interval | 10/12 cycles | 10/12 cycles | 2..1024 cycles | 200 ms | 1..1024 cycles | 200 ms | 200 ms | 600..1600ms | 190..420ms |
Continuous measurement | x | x | x | -- | x | -- | -- | -- | -- |
Measurement input voltage (max.) L-L | 690 (832) V | 690 (832) V | 690 (832) V | 500 (550) V | 690 (1000) V | 500 (600) V | 500 (600) V | 690 (1040) V | 690 (1040) V |
Measurement input current (max.) | 1 and 5A (7,5A) | 1 and 5A (7,5A) | 1 and 5A (7.5A) | 1 and 5A (6A) | 1...5A (10A) | 1 or 5A (6A) | 1 or 5A (6A) | 1...6A (11.25A) | 1...6A (11.25A) |
Frequency range | 45-50-65, 55-60-65 Hz | 45-50-65, 55-60-65 Hz | 45-50/60-65Hz | 45-50/60-65Hz | 10-70, 45-65, 10-140Hz with nominal 50/60Hz | 45-50/60-65Hz | 45-50/60-65Hz | 45-50/60-65Hz | 10-16.7-50/60-65Hz |
Power supply AC/DC | 110..230VAC, 130..230VDC or 110..200VAC/DC or 24..48 VDC |
110..230VAC, 130..230VDC or 110..200VAC/DC or 24..48 VDC |
24...230VDC 100..230VAC ±15% |
73-264V or 20..70V AC/DC | 100..230V ±15% | 85..253V or 20..70V | 85..253V or 20..70V | 85..253V or 20..70V | 85...230V±15% or 24..60V±15% |
Measured Quantities | |||||||||
Basic system quantities | x | x | x | x | x | x | x | x | x |
Mean values | 1s..60min | 1s..60min | 1s..60min | 1..60min | 1s..60min | 1..60min | 1..60min | -- | -- |
Min/Max values with time reference | x | x | x | x | x | with EMMOD203 | with EMMOD203 | -- | -- |
Harmonic analysis | 2. bis 50. | 2. bis 50. | 2nd up to 50th | 2nd up to 15th | 2nd up to 50th | -- | 2nd up to 15th | -- | -- |
Extended reactive power analysis | x | x | x | -- | -- | -- | -- | -- | -- |
Phase angle of voltages | x | x | x | -- | -- | -- | -- | -- | -- |
System unbalance | U+I (3L+4L) | U+I (3L+4L) | U+I (3L+4L) | -- | U (4L) | -- | U (4L) | -- | -- |
Energy meters P/Q (HT/LT) | System, phase (incoming) +12 free prog. | System, phase (incoming) +12 free prog. | System, phase (incoming) | system, phase or HT/LT | system | system | system | -- | bis 4 |
Universal meters via I/O's | -- | -- | x(max. 7) | -- | x(max. 12) | -- | -- | -- | -- |
Operating hours counters | -- | -- | 3+1 | -- | 1 | -- | -- | -- | -- |
Uncertainty | |||||||||
Voltage, current | ±0,2% | ±0,2% | ±0,1% | ±0,25 | ±0,1% | ±0,5% | ±0,2% | ±0,2% | ±0,2% |
Active, reactive, apparent power | ±0,5% | ±0,5% | ±0,2% | ±0,5 | ±0,2% | ±1% | ±0,5% | ±0,5% | ±0,5% |
Active / reactive energy (IEC 62053) | Class 1.0 / 2 | Class 1.0 / 2 | Class 0.5S / 2 | -- | Class 1.0 / 2 | -- | -- | -- | Class 1.0 / 2 |
Monitoring Functions | |||||||||
Limit values | up to 12 | up to 12 | up to 16 | 2+2 | up to 64 | 2 | 2 | -- | -- |
Boolean logic (logic module) | 8 functions | 8 functions | 4 functions | -- | 32 functions | -- | -- | -- | -- |
Recording Functions | (optional) | (optional) | with EMMOD.. | with EMMOD.. | |||||
Load profiles (mean values) | x | x | x | x | x | 201/203 | 201/203 | -- | -- |
Min/max values per averaging interval | x | x | x | -- | x | -- | 203 | -- | -- |
Events / alarms | x | x | x | -- | x | -- | -- | -- | -- |
Disturbance recording (RMS values) | -- | -- | x(e2-cycle-values) | x(e300ms values) | -- | -- | -- | -- | -- |
Meter readings (calendar based) | -- | -- | x | -- | x | -- | -- | -- | -- |
Interfaces | with EMMOD.. | with EMMOD.. | |||||||
Ethernet, Modbus/TCP | -- | -- | x(optional) | x(optional) | x(optional) | 203 | 203 | -- | -- |
Profibus DP | -- | -- | -- | V005 | -- | 204 | 204 | -- | -- |
Modbus | 2,4..115,2kBd | 2,4..115,2kBd | 2,4..115,2kBd | 1,2..19,2kBd | 1,2..115,2kBd | 201: 1,2..19,2kBd | 201: 1,2..19,2kBd | -- | 1,2..9,6kBd |
LON | -- | -- | -- | V004 | -- | 205 | 205 | -- | DME400 |
Inputs / Outputs | with EMMOD.. | with EMMOD.. | |||||||
Digital inputs | 1 | 1 | 1..7 | 0, 1 | 0, 3, 6, 9, 12 | 0, 1, 2 | 0, 1, 2 | -- | -- |
Digital outputs | 2 | 2 | 1..7 | 0, 2 | 0, 3, 6, 9, 12 | 2 | 2 | 0, 2, 4 | |
Analog inputs | -- | -- | -- | -- | 0, 2, 4, 6, 8 | -- | -- | -- | -- |
Analog outputs | 0, 2, 4 | 0, 2, 4 | 0, 4 | 2, 4 | 0, 2, 4, 6, 8 | 0, 2 | 0, 2 | 1, 2, 3 | 0, 2 ,4 |
Relays | 0, 2, 4, 6, 8 | 0, 2, 4, 6, 8 | 1, 3 | -- | 2 | -- | -- | -- | -- |
Display | TFT display | TFT display | LED or TFT | with graphic display | via A200 | ||||
User-definable displays | -- | -- | x | -- | x | -- | ( x ) | -- | -- |
Display of limit states | Alarm list | Alarm list | 4 LED's + plain text or alarm list | -- | State +plain text | -- | -- | -- | -- |
Front W x H | 144 x 144 mm | 144 x 144 mm | 96 x 96 mm | 144 x 144 mm | 186 x 66 mm | 96 x 96 / 144 x 144 mm | 96 x 96 / 144 x 144 mm | -- | -- |
Installation depth (incl. module) | 65,2 | 65,2 | 105 mm | 59 mm | -- | 46 (65) mm | 46 (65) mm | -- | -- |